Basic Info.
Application
Construction, Underground, Industrial, Power Station
Voltage
Low and Medium Voltage Cable
Material Shape
Round Wire
Wire Core Material
Bare Copper Wire
Certification
ISO, CCC, CE, RoHS
Product Description
XLPE Insulated Electric Cable -- Rated voltage 3.6/6KV-26/35KVCable construction: , Model, Name & Application:Model | Name | Application |
YJV | , Copper conductor,XLPE insulated,PVC sheathed electric cable | ,. For laying indoors,in tunnels,cable trench,etc,unable to bear external mechanical forces. . Single core cable in magnetic duct is not permissible. |
YJLV | , Aluminium conductor,XLPE insulated,PVC sheathed electric cable |
YJY | , Copper conductor,XLPE insulated,PE sheathed electric cable |
YJLY | , Aluminium conductor,XLPE insulated,PE sheathed electric cable |
YJV22 | , Copper conductor,XLPE insulated,Steel tape armoured,PVC sheathed electric cable | ,,. For laying indoors,in tunnels,cable trench,or direct in ground. . Able to bear external mechanical forces,but unable to bear large pulling forces. |
YJLV22 | , Aluminium conductor,XLPE insulated,Steel tape armoured,PVC sheathed electric cable |
YJV23 | , Copper conductor,XLPE insulated,Steel tape armoured,PE sheathed electric cable |
YJLV23 | , Aluminium conductor,XLPE insulated,Steel tape armoured,PE sheathed electric cable |
YJV32 | , Copper conductor,XLPE insulated,Steel wire armoured,PVC sheathed electric cable | ,,,. For laying indoors,in tunnels,cable trench,vertical shaft or direct in ground. . Able to bear external mechanical forces and some pulling forces. |
YJLV32 | , Aluminium conductor,XLPE insulated,Steel wire armoured,PVC sheathed electric cable |
YJV33 | , Copper conductor,XLPE insulated,Steel wire armoured,PE sheathed electric cable |
YJLV33 | , Aluminium conductor,XLPE insulated,Steel wire armoured,PE sheathed electric cable |
Product data:3.6/6KV, , /3.6/6KV, 1-Core XLPE Insulated, PVC/PE Sheathed Power CableNominal cross-sectional area of conductor (mm2) | Insulation thickness (mm) | YJV, YJLV, YJY, YJLY | YJV22, YJLV22, YJV23, YJLV23 | YJV32,YJLV32,YJV33,YJLV33 |
Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) |
YJV, YJY | YJLV, YJLY | YJV22, YJV23 | YJLV22, YJLV23 | YJV32, YJV33 | YJLV32, YJLV33 |
1×25 | 2.5 | 17.9 | 560 | 390 | 21.7 | 700 | 550 | 24.7 | 1340 | 1190 |
1×35 | 2.5 | 18.9 | 680 | 480 | 22.6 | 820 | 610 | 25.8 | 1490 | 1290 |
1×50 | 2.5 | 20.3 | 860 | 550 | 24.0 | 990 | 690 | 27.2 | 1720 | 1420 |
1×70 | 2.5 | 21.9 | 1080 | 650 | 25.4 | 1220 | 790 | 28.8 | 2010 | 1590 |
1×95 | 2.5 | 23.7 | 1350 | 760 | 27.2 | 1490 | 920 | 30.6 | 2350 | 1770 |
1×120 | 2.5 | 25.2 | 1610 | 870 | 28.7 | 1770 | 1040 | 32.1 | 2680 | 1950 |
1×150 | 2.5 | 27.0 | 1920 | 990 | 31.7 | 2240 | 1330 | 34.9 | 3070 | 2160 |
1×185 | 2.5 | 28.6 | 2290 | 1140 | 33.3 | 2600 | 1480 | 36.5 | 3480 | 2360 |
1×240 | 2.6 | 31.2 | 2860 | 1370 | 35.9 | 3180 | 1730 | 39.1 | 4140 | 2680 |
1×300 | 2.8 | 34.0 | 3500 | 1640 | 38.7 | 3810 | 1990 | 41.9 | 4840 | 3020 |
1×400 | 3.0 | 37.6 | 4610 | 2140 | 42.5 | 4840 | 2420 | 45.6 | 6320 | 3890 |
1×500 | 3.2 | 41.3 | 5700 | 2610 | 46.3 | 5860 | 2830 | 49.3 | 7470 | 4440 |
1×630 | 3.2 | 44.9 | 6990 | 3090 | 50.0 | 7200 | 3380 | 53.1 | 8940 | 5120 |
3.6/6KV, , /3.6/6KV, 3-Core XLPE Insulated, PVC/PE Sheathed Power CableNominal cross-sectional area of conductor (mm2) | Insulation thickness (mm) | YJV, YJLV, YJY, YJLY | YJV22, YJLV22, YJV23, YJLV23 | YJV32,YJLV32,YJV33,YJLV33 |
Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) |
YJV, YJY | YJLV, YJLY | YJV22, YJV23 | YJLV22, YJLV23 | YJV32, YJV33 | YJLV32, YJLV33 |
3×25 | 2.5 | 35.8 | 1750 | 1280 | 40.5 | 2760 | 2300 | 42.7 | 3620 | 3160 |
3×35 | 2.5 | 38.1 | 2130 | 1470 | 43.0 | 3210 | 2550 | 46.2 | 4140 | 3490 |
3×50 | 2.5 | 41.1 | 2670 | 1740 | 46.1 | 3830 | 2890 | 49.3 | 4860 | 3940 |
3×70 | 2.5 | 44.5 | 3390 | 2090 | 49.7 | 4650 | 3340 | 52.9 | 5770 | 4480 |
3×95 | 2.5 | 48.5 | 4250 | 2470 | 53.8 | 5630 | 3850 | 57.0 | 6870 | 5120 |
3×120 | 2.5 | 51.7 | 5090 | 2850 | 57.2 | 6550 | 4310 | 60.4 | 7870 | 5650 |
3×150 | 2.5 | 55.4 | 6120 | 3310 | 60.9 | 7650 | 4840 | 64.2 | 9090 | 6320 |
3×185 | 2.5 | 58.8 | 7270 | 3800 | 64.5 | 8890 | 5430 | 67.8 | 10460 | 7050 |
3×240 | 2.6 | 64.6 | 9090 | 4600 | 70.5 | 10860 | 6370 | 75.1 | 13380 | 8940 |
3×300 | 2.8 | 70.6 | 11120 | 5510 | 76.7 | 13230 | 7610 | 81.3 | 15680 | 10130 |
3×400 | 3.0 | 78.4 | 15190 | 7750 | 86.2 | 17830 | 10440 | 89.5 | 19320 | 11930 |
3×500 | 3.2 | 86.2 | 17131 | 8045 | 94.3 | 20087 | 11256 | 97.6 | 23060 | 13820 |
3×630 | 3.2 | 94.0 | 21037 | 9749 | 102.4 | 23952 | 13166 | 105.7 | 27690 | 16050 |
6/6 6/10KV, , /6/6 6/10KV, 1-Core XLPE Insulated, PVC/PE Sheathed Power CableNominal cross-sectional area of conductor (mm2) | Insulation thickness (mm) | YJV, YJLV, YJY, YJLY | YJV22, YJLV22, YJV23, YJLV23 | YJV32,YJLV32,YJV33,YJLV33 |
Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) |
YJV, YJY | YJLV, YJLY | YJV22, YJV23 | YJLV22, YJLV23 | YJV32, YJV33 | YJLV32, YJLV33 |
1×25 | 3.4 | 19.8 | 609 | 458 | 23.4 | 919 | 767 | 26.6 | 1643 | 1384 |
1×35 | 3.4 | 20.8 | 729 | 514 | 24.4 | 1055 | 840 | 27.6 | 1821 | 1499 |
1×50 | 3.4 | 22.3 | 876 | 585 | 25.7 | 1219 | 929 | 29.1 | 2027 | 1628 |
1×70 | 3.4 | 23.8 | 1092 | 681 | 27.2 | 1458 | 1047 | 30.6 | 2329 | 1810 |
1×95 | 3.4 | 25.7 | 1388 | 805 | 29.1 | 1780 | 1197 | 32.5 | 2689 | 1999 |
1×120 | 3.4 | 27.1 | 1651 | 913 | 31.9 | 2312 | 1575 | 33.9 | 3037 | 2192 |
1×150 | 3.4 | 28.7 | 1970 | 1043 | 33.5 | 2670 | 1743 | 35.7 | 3419 | 2384 |
1×185 | 3.4 | 30.4 | 2271 | 1165 | 35.2 | 3007 | 1901 | 38.4 | 4147 | 2869 |
1×240 | 3.4 | 32.9 | 2830 | 1382 | 37.7 | 3621 | 2173 | 40.9 | 4842 | 3222 |
1×300 | 3.4 | 35.3 | 3502 | 1642 | 39.9 | 4330 | 2470 | 43.3 | 5637 | 3606 |
1×400 | 3.4 | 38.5 | 4406 | 1991 | 43.3 | 5281 | 2866 | 46.7 | 6701 | 4115 |
1×500 | 3.4 | 42.0 | 5515 | 2418 | 47.0 | 6442 | 3345 | 50.2 | 7992 | 4724 |
1×630 | 3.4 | 45.6 | 6754 | 2883 | 50.8 | 7766 | 3895 | 54.0 | 9457 | 5414 |
6/6 6/10KV, , /6/6 6/10KV, 3-Core XLPE Insulated, PVC/PE Sheathed Power CableNominal cross-sectional area of conductor (mm2) | Insulation thickness (mm) | YJV, YJLV, YJY, YJLY | YJV22, YJLV22, YJV23, YJLV23 | YJV32,YJLV32,YJV33,YJLV33 |
Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) |
YJV, YJY | YJLV, YJLY | YJV22, YJV23 | YJLV22, YJLV23 | YJV32, YJV33 | YJLV32, YJLV33 |
3×25 | 3.4 | 39.8 | 1927 | 1451 | 44.8 | 2785 | 2322 | 48.0 | 4229 | 3766 |
3×35 | 3.4 | 42.2 | 2136 | 1639 | 47.4 | 3224 | 2569 | 50.6 | 4771 | 4117 |
3×50 | 3.4 | 45.2 | 2805 | 1874 | 50.4 | 3795 | 2909 | 53.6 | 5456 | 4571 |
3×70 | 3.4 | 48.6 | 3497 | 2193 | 54.0 | 4586 | 3335 | 57.2 | 6352 | 5101 |
3×95 | 3.4 | 52.7 | 4483 | 2653 | 57.9 | 5631 | 3857 | 61.1 | 7539 | 5765 |
3×120 | 3.4 | 55.9 | 5340 | 3040 | 61.3 | 6561 | 4317 | 64.5 | 8578 | 6334 |
3×150 | 3.4 | 59.6 | 6398 | 3503 | 65.4 | 7732 | 4911 | 68.6 | 9901 | 7080 |
3×185 | 3.4 | 63.0 | 7241 | 3946 | 68.8 | 8828 | 5460 | 72.0 | 11095 | 7727 |
3×240 | 3.4 | 68.3 | 9234 | 4729 | 74.3 | 10769 | 6360 | 77.5 | 13254 | 8844 |
3×300 | 3.4 | 73.3 | 11337 | 5586 | 80.9 | 13069 | 7406 | 84.2 | 16678 | 11015 |
3×400 | 3.4 | 80.3 | 14174 | 6822 | 88.1 | 16832 | 9480 | 91.4 | 20051 | 12698 |
3×500 | 3.4 | 87.9 | 17730 | 8299 | 95.2 | 20687 | 11256 | 99.2 | 24211 | 14780 |
3×630 | 3.4 | 95.8 | 21736 | 9949 | 104.0 | 24952 | 13165 | 107.3 | 28839 | 17052 |
8.7/10 8.7/15KV, , /8.7/10 8.7/15KV, 1-Core XLPE Insulated, PVC/PE Sheathed Power CableNominal cross-sectional area of conductor (mm2) | Insulation thickness (mm) | YJV, YJLV, YJY, YJLY | YJV22, YJLV22, YJV23, YJLV23 | YJV32,YJLV32,YJV33,YJLV33 |
Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) |
YJV, YJY | YJLV, YJLY | YJV22, YJV23 | YJLV22, YJLV23 | YJV32, YJV33 | YJLV32, YJLV33 |
1×25 | 4.5 | 22.0 | 696 | 544 | 25.6 | 919 | 767 | 29.0 | 1846 | 1587 |
1×35 | 4.5 | 23.0 | 819 | 604 | 26.6 | 1055 | 840 | 30.0 | 2026 | 1704 |
1×50 | 4.5 | 24.5 | 970 | 679 | 27.9 | 1219 | 929 | 31.5 | 2237 | 1839 |
1×70 | 4.5 | 26.2 | 1191 | 780 | 30.8 | 1458 | 1047 | 33.0 | 2520 | 2002 |
1×95 | 4.5 | 27.9 | 1493 | 910 | 32.7 | 1780 | 1197 | 34.9 | 2911 | 2220 |
1×120 | 4.5 | 29.5 | 1760 | 1023 | 34.1 | 2312 | 1575 | 37.5 | 3690 | 2770 |
1×150 | 4.5 | 31.1 | 2085 | 1158 | 35.9 | 2670 | 1743 | 39.1 | 4005 | 2907 |
1×185 | 4.5 | 32.8 | 2391 | 1285 | 37.6 | 3007 | 1901 | 40.8 | 4402 | 3124 |
1×240 | 4.5 | 35.3 | 2873 | 1525 | 39.9 | 3621 | 2173 | 43.1 | 5104 | 3485 |
1×300 | 4.5 | 37.7 | 3657 | 1798 | 42.5 | 4330 | 2470 | 45.7 | 5908 | 3877 |
1×400 | 4.5 | 40.9 | 4571 | 2156 | 45.7 | 5281 | 2866 | 48.9 | 6982 | 4396 |
1×500 | 4.5 | 44.4 | 5692 | 2595 | 49.4 | 6442 | 3345 | 52.6 | 8287 | 5018 |
1×630 | 4.5 | 48.0 | 6945 | 3074 | 53.4 | 7766 | 3895 | 56.6 | 9789 | 5746 |
8.7/10 8.7/15KV, , /8.7/10 8.7/15KV, 3-Core XLPE Insulated, PVC/PE Sheathed Power CableNominal cross-sectional area of conductor (mm2) | Insulation thickness (mm) | YJV, YJLV, YJY, YJLY | YJV22, YJLV22, YJV23, YJLV23 | YJV32,YJLV32,YJV33,YJLV33 |
Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) |
YJV, YJY | YJLV, YJLY | YJV22, YJV23 | YJLV22, YJLV23 | YJV32, YJV33 | YJLV32, YJLV33 |
3×25 | 4.5 | 45.0 | 2917 | 1747 | 50.2 | 3201 | 2739 | 52.4 | 4841 | 4378 |
3×35 | 4.5 | 47.3 | 2616 | 1947 | 52.3 | 3646 | 2991 | 55.7 | 5394 | 4740 |
3×50 | 4.5 | 50.3 | 3144 | 2223 | 55.7 | 4269 | 3383 | 58.9 | 6107 | 5222 |
3×70 | 4.5 | 53.8 | 3879 | 2586 | 59.4 | 5082 | 3831 | 62.6 | 7066 | 5815 |
3×95 | 4.5 | 57.6 | 4872 | 3051 | 63.2 | 6159 | 4285 | 66.4 | 8276 | 6501 |
3×120 | 4.5 | 60.9 | 5753 | 3458 | 66.7 | 7115 | 4870 | 69.9 | 9312 | 7068 |
3×150 | 4.5 | 64.5 | 6837 | 3945 | 70.5 | 8296 | 5475 | 73.7 | 10636 | 7814 |
3×185 | 4.5 | 68.1 | 7900 | 4429 | 74.1 | 9429 | 6061 | 77.3 | 11879 | 8510 |
3×240 | 4.5 | 73.3 | 9719 | 5230 | 79.5 | 11450 | 7041 | 84.2 | 15060 | 10650 |
3×300 | 4.5 | 78.4 | 11862 | 6154 | 86.2 | 14508 | 8845 | 89.5 | 17597 | 11934 |
3×400 | 4.5 | 85.3 | 14795 | 7402 | 93.5 | 17695 | 10343 | 96.8 | 21109 | 13756 |
3×500 | 4.5 | 93.0 | 18381 | 8950 | 101.2 | 21503 | 12072 | 104.5 | 25267 | 15836 |
3×630 | 4.5 | 100.7 | 22396 | 10609 | 109.3 | 25869 | 14082 | 112.6 | 29892 | 18105 |
12/20KV, , /12/20KV, 1-Core XLPE Insulated, PVC/PE Sheathed Power CableNominal cross-sectional area of conductor (mm2) | Insulation thickness (mm) | YJV, YJLV, YJY, YJLY | YJV22, YJLV22, YJV23, YJLV23 | YJV32,YJLV32,YJV33,YJLV33 |
Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) |
YJV, YJY | YJLV, YJLY | YJV22, YJV23 | YJLV22, YJLV23 | YJV32, YJV33 | YJLV32, YJLV33 |
1×35 | 5.5 | 25.4 | 930 | 720 | 30.1 | 1410 | 1200 | 32.2 | 2030 | 1820 |
1×50 | 5.5 | 26.8 | 1160 | 850 | 31.5 | 1630 | 1320 | 33.6 | 2280 | 1980 |
1×70 | 5.5 | 28.4 | 1410 | 980 | 33.1 | 1890 | 1460 | 35.2 | 2580 | 2150 |
1×95 | 5.5 | 30.2 | 1690 | 1110 | 34.9 | 2210 | 1640 | 37.0 | 2950 | 2370 |
1×120 | 5.5 | 31.7 | 1980 | 1240 | 36.4 | 2510 | 1780 | 38.5 | 3280 | 2550 |
1×150 | 5.5 | 33.4 | 2310 | 1380 | 38.1 | 2880 | 1970 | 40.2 | 3680 | 2770 |
1×185 | 5.5 | 35.0 | 2700 | 1550 | 39.7 | 3270 | 2150 | 41.8 | 4110 | 2990 |
1×240 | 5.5 | 37.4 | 3290 | 1800 | 42.1 | 3900 | 2440 | 45.4 | 5150 | 3690 |
1×300 | 5.5 | 39.8 | 3910 | 2050 | 44.7 | 4590 | 2770 | 47.9 | 5930 | 4110 |
1×400 | 5.5 | 43.0 | 5030 | 2550 | 48.1 | 5670 | 3250 | 51.3 | 7130 | 4690 |
1×500 | 5.5 | 46.2 | 6120 | 3030 | 51.4 | 6760 | 3730 | 54.6 | 8320 | 5280 |
1×630 | 5.5 | 49.8 | 7440 | 3540 | 55.2 | 8150 | 4320 | 58.4 | 9830 | 6010 |
12/20KV, , /12/20KV, 3-Core XLPE Insulated, PVC/PE Sheathed Power CableNominal cross-sectional area of conductor (mm2) | Insulation thickness (mm) | YJV, YJLV, YJY, YJLY | YJV22, YJLV22, YJV23, YJLV23 | YJV32,YJLV32,YJV33,YJLV33 |
Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) |
YJV, YJY | YJLV, YJLY | YJV22, YJV23 | YJLV22, YJLV23 | YJV32, YJV33 | YJLV32, YJLV33 |
3×35 | 5.5 | 52.0 | 3230 | 2570 | 57.4 | 4270 | 3620 | 60.7 | 5970 | 5330 |
3×50 | 5.5 | 55.0 | 3840 | 2900 | 60.6 | 4930 | 4010 | 63.8 | 6730 | 5810 |
3×70 | 5.5 | 58.1 | 4640 | 3330 | 64.1 | 5830 | 4540 | 67.3 | 7720 | 6430 |
3×95 | 5.5 | 62.3 | 5570 | 3800 | 68.2 | 6850 | 5090 | 72.8 | 9640 | 7890 |
3×120 | 5.5 | 65.6 | 6480 | 4240 | 71.5 | 7850 | 5640 | 76.1 | 10800 | 8580 |
3×150 | 5.5 | 69.2 | 7560 | 4750 | 75.3 | 9040 | 6260 | 79.9 | 12180 | 9410 |
3×185 | 5.5 | 72.7 | 8780 | 5320 | 78.9 | 10300 | 6890 | 83.5 | 13600 | 10180 |
3×240 | 5.5 | 78.0 | 10680 | 6180 | 85.7 | 13120 | 8690 | 89.0 | 15850 | 11420 |
3×300 | 5.5 | 83.0 | 12720 | 7100 | 91.0 | 15350 | 9810 | 94.3 | 18260 | 12720 |
3×400 | 5.5 | 90.0 | 16280 | 8790 | 98.2 | 18940 | 11560 | 101.5 | 22100 | 14710 |
3×500 | 5.5 | 96.8 | 18820 | 9580 | 105.3 | 22530 | 13300 | 108.6 | 25950 | 16710 |
3×630 | 5.5 | 104.6 | 22950 | 11310 | 113.4 | 27000 | 15370 | 116.7 | 30690 | 19050 |
18/20 18/30KV, , /18/20 18/30KV, 1-Core XLPE Insulated, PVC/PE Sheathed Power CableNominal cross-sectional area of conductor (mm2) | Insulation thickness (mm) | YJV, YJLV, YJY, YJLY | YJV22, YJLV22, YJV23, YJLV23 | YJV32,YJLV32,YJV33,YJLV33 |
Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) |
YJV, YJY | YJLV, YJLY | YJV22, YJV23 | YJLV22, YJLV23 | YJV32, YJV33 | YJLV32, YJLV33 |
1×35 | 8.0 | 31.9 | 1240 | 1020 | - | - | - | - | - | - |
1×50 | 8.0 | 33.3 | 1560 | 1250 | 35.4 | 2060 | 1760 | 38.8 | 2910 | 2610 |
1×70 | 8.0 | 34.9 | 1840 | 1400 | 38.6 | 2340 | 1910 | 40.7 | 3240 | 2820 |
1×95 | 8.0 | 36.7 | 2140 | 1550 | 40.1 | 2680 | 2100 | 42.3 | 3610 | 3030 |
1×120 | 8.0 | 38.2 | 2450 | 1700 | 41.8 | 3020 | 2290 | 43.9 | 4370 | 3640 |
1×150 | 8.0 | 39.9 | 2790 | 1860 | 43.4 | 3400 | 2490 | 46.7 | 4810 | 3900 |
1×185 | 8.0 | 41.5 | 3200 | 2050 | 45.3 | 3810 | 2690 | 48.5 | 5270 | 4150 |
1×240 | 8.0 | 44.0 | 3800 | 2310 | 47.6 | 4490 | 3030 | 50.7 | 6040 | 4580 |
1×300 | 8.0 | 46.3 | 4460 | 2600 | 50.2 | 5180 | 3300 | 53.5 | 6810 | 4990 |
1×400 | 8.0 | 49.6 | 5530 | 3060 | 53.4 | 6310 | 3880 | 56.7 | 8050 | 5620 |
1×500 | 8.0 | 52.8 | 6160 | 3560 | 57.0 | 7430 | 4390 | 60.3 | 9280 | 6250 |
1×630 | 8.0 | 56.4 | 8020 | 4120 | 61.2 | 8860 | 5030 | 64.3 | 10830 | 7010 |
18/20 18/30KV, , /18/20 18/30KV, 3-Core XLPE Insulated, PVC/PE Sheathed Power CableNominal cross-sectional area of conductor (mm2) | Insulation thickness (mm) | YJV, YJLV, YJY, YJLY | YJV22, YJLV22, YJV23, YJLV23 | YJV32,YJLV32,YJV33,YJLV33 |
Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) |
YJV, YJY | YJLV, YJLY | YJV22, YJV23 | YJLV22, YJLV23 | YJV32, YJV33 | YJLV32, YJLV33 |
3×50 | 8.0 | 68.4 | 5290 | 4350 | 75.1 | 7200 | 6250 | 79.7 | 9790 | 8870 |
3×70 | 8.0 | 72.5 | 6240 | 4930 | 78.7 | 8230 | 6910 | 83.3 | 10900 | 9610 |
3×95 | 8.0 | 75.9 | 7360 | 5580 | 84.0 | 9410 | 7620 | 87.4 | 12220 | 10470 |
3×120 | 8.0 | 79.4 | 8350 | 6100 | 87.5 | 11120 | 8870 | 90.8 | 13440 | 11220 |
3×150 | 8.0 | 82.6 | 9520 | 6410 | 91.3 | 12400 | 9580 | 94.6 | 14880 | 12100 |
3×185 | 8.0 | 84.4 | 10830 | 7370 | 94.9 | 13910 | 10450 | 98.2 | 16420 | 12990 |
3×240 | 8.0 | 91.4 | 12810 | 8300 | 100.3 | 16080 | 11590 | 103.7 | 18770 | 14340 |
3×300 | 8.0 | 96.7 | 14920 | 9300 | 105.6 | 18500 | 12850 | 108.9 | 21250 | 15710 |
3×400 | 8.0 | 103.8 | 18110 | 10620 | 112.8 | 21920 | 14410 | 116.1 | 25260 | 17870 |
3×500 | 8.0 | 111.1 | 20990 | 11780 | 119.3 | 25970 | 16330 | 123.2 | 29260 | 20030 |
3×630 | 8.0 | 119.2 | 25290 | 13650 | 128.9 | 31250 | 18970 | 131.3 | 34170 | 22530 |
21/35KV, , /21/35KV, 1-Core XLPE Insulated, PVC/PE Sheathed Power CableNominal cross-sectional area of conductor (mm2) | Insulation thickness (mm) | YJV, YJLV, YJY, YJLY | YJV22, YJLV22, YJV23, YJLV23 | YJV32,YJLV32,YJV33,YJLV33 |
Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) |
YJV, YJY | YJLV, YJLY | YJV22, YJV23 | YJLV22, YJLV23 | YJV32, YJV33 | YJLV32, YJLV33 |
1×50 | 9.3 | 36.1 | 1590 | 1290 | 40.5 | 2370 | 2070 | 43.0 | 3200 | 2890 |
1×70 | 9.3 | 37.7 | 1840 | 1420 | 42.2 | 2670 | 2250 | 45.7 | 3920 | 3490 |
1×95 | 9.3 | 39.5 | 2160 | 1580 | 44.1 | 3030 | 2460 | 47.6 | 4340 | 3760 |
1×120 | 9.3 | 41.0 | 2450 | 1720 | 45.6 | 3350 | 2620 | 49.1 | 4710 | 3980 |
1×150 | 9.3 | 42.7 | 2810 | 1890 | 47.4 | 3750 | 2840 | 50.9 | 5160 | 4250 |
1×185 | 9.3 | 44.3 | 3190 | 2070 | 49.0 | 4190 | 3060 | 52.6 | 5660 | 4530 |
1×240 | 9.3 | 46.7 | 3810 | 2350 | 51.6 | 4860 | 3400 | 55.1 | 6400 | 4950 |
1×300 | 9.3 | 49.1 | 4460 | 2640 | 54.1 | 5590 | 3770 | 57.6 | 7220 | 5390 |
1×400 | 9.3 | 52.3 | 5510 | 3080 | 57.4 | 6710 | 4280 | 61.0 | 8440 | 6020 |
1×500 | 9.3 | 55.5 | 6570 | 3540 | 60.7 | 7870 | 4840 | 64.2 | 9720 | 6690 |
1×630 | 9.3 | 59.1 | 7910 | 4080 | 64.4 | 9290 | 5470 | 68.0 | 11260 | 7440 |
21/35KV, , /21/35KV, 3-Core XLPE Insulated, PVC/PE Sheathed Power CableNominal cross-sectional area of conductor (mm2) | Insulation thickness (mm) | YJV, YJLV, YJY, YJLY | YJV22, YJLV22, YJV23, YJLV23 | YJV32,YJLV32,YJV33,YJLV33 |
Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) |
YJV, YJY | YJLV, YJLY | YJV22, YJV23 | YJLV22, YJLV23 | YJV32, YJV33 | YJLV32, YJLV33 |
3×50 | 9.3 | 75.1 | 5560 | 4640 | 82.7 | 8260 | 7340 | 86.0 | 10890 | 9960 |
3×70 | 9.3 | 78.6 | 6450 | 5160 | 86.3 | 9280 | 7990 | 89.6 | 12030 | 10740 |
3×95 | 9.3 | 82.5 | 7490 | 5730 | 90.4 | 10500 | 8740 | 93.7 | 13430 | 11670 |
3×120 | 9.3 | 85.7 | 8470 | 6260 | 93.7 | 11630 | 9420 | 97.0 | 14630 | 12420 |
3×150 | 9.3 | 89.4 | 9640 | 6860 | 97.5 | 12970 | 10200 | 100.8 | 16100 | 13330 |
3×185 | 9.3 | 92.8 | 10920 | 7500 | 101.1 | 14420 | 11010 | 104.4 | 17680 | 14260 |
3×240 | 9.3 | 98.1 | 12950 | 8520 | 106.6 | 16690 | 12260 | 109.9 | 20140 | 15710 |
3×300 | 9.3 | 103.1 | 15060 | 9520 | 111.8 | 18990 | 13450 | 115.1 | 22610 | 17070 |
3×400 | 9.3 | 110.1 | 18520 | 11120 | 119.0 | 22820 | 15430 | 122.3 | 26680 | 19290 |
3×500 | 9.3 | 116.9 | 21990 | 12760 | 126.1 | 26630 | 17390 | 129.4 | 30750 | 21520 |
3×630 | 9.3 | 124.7 | 26350 | 14710 | 134.2 | 31340 | 19700 | 137.5 | 35730 | 24090 |
26/35KV, , /26/35KV, 1-Core XLPE Insulated, PVC/PE Sheathed Power CableNominal cross-sectional area of conductor (mm2) | Insulation thickness (mm) | YJV, YJLV, YJY, YJLY | YJV22, YJLV22, YJV23, YJLV23 | YJV32,YJLV32,YJV33,YJLV33 |
Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) |
YJV, YJY | YJLV, YJLY | YJV22, YJV23 | YJLV22, YJLV23 | YJV32, YJV33 | YJLV32, YJLV33 |
1×50 | 10.5 | 38.7 | 1727 | 1427 | 43.7 | 2600 | 2320 | 46.9 | 4030 | 3490 |
1×70 | 10.5 | 40.2 | 1980 | 1570 | 45.2 | 2890 | 2480 | 48.4 | 4380 | 3710 |
1×95 | 10.5 | 42.1 | 2335 | 1750 | 47.1 | 3270 | 2690 | 50.3 | 4830 | 3990 |
1×120 | 10.5 | 43.7 | 2650 | 1910 | 48.7 | 3600 | 2860 | 51.9 | 5250 | 4260 |
1×150 | 10.5 | 45.3 | 3016 | 2090 | 50.5 | 4020 | 3090 | 53.7 | 5730 | 4540 |
1×185 | 10.5 | 47.0 | 3377 | 2270 | 52.0 | 4410 | 3305 | 55.2 | 6160 | 4790 |
1×240 | 10.5 | 49.3 | 3996 | 2550 | 54.7 | 5110 | 3660 | 57.9 | 6940 | 5230 |
1×300 | 10.5 | 51.7 | 4733 | 2870 | 57.1 | 5900 | 4040 | 60.3 | 7810 | 5690 |
1×400 | 10.5 | 54.9 | 5723 | 3308 | 60.5 | 6340 | 4520 | 63.7 | 8990 | 6310 |
1×500 | 10.5 | 59.8 | 7068 | 3970 | 65.6 | 8380 | 5290 | 68.8 | 10500 | 7140 |
1×630 | 10.5 | 63.6 | 8418 | 4550 | 69.2 | 9790 | 5910 | 72.6 | 12080 | 7950 |
26/35KV, , /26/35KV, 3-Core XLPE Insulated, PVC/PE Sheathed Power CableNominal cross-sectional area of conductor (mm2) | Insulation thickness (mm) | YJV, YJLV, YJY, YJLY | YJV22, YJLV22, YJV23, YJLV23 | YJV32,YJLV32,YJV33,YJLV33 |
Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) | Approx. overall diameter of cable (mm) | Approx. weight of cable (kg/km) |
YJV, YJY | YJLV, YJLY | YJV22, YJV23 | YJLV22, YJLV23 | YJV32, YJV33 | YJLV32, YJLV33 |
3×50 | 10.5 | 80.8 | 6030 | 5150 | 88.6 | 8700 | 7820 | 91.9 | 12620 | 11740 |
3×70 | 10.5 | 84.2 | 6900 | 5650 | 92.0 | 9690 | 8430 | 95.5 | 13820 | 12560 |
3×95 | 10.5 | 88.1 | 8060 | 6282 | 86.3 | 11050 | 9270 | 99.6 | 15360 | 13590 |
3×120 | 10.5 | 91.3 | 9070 | 6830 | 99.7 | 12210 | 9970 | 103.0 | 16700 | 14460 |
3×150 | 10.5 | 94.9 | 10290 | 7470 | 103.3 | 13560 | 10730 | 106.6 | 18280 | 15460 |
3×185 | 10.5 | 98.4 | 11490 | 8120 | 107.0 | 14880 | 11500 | 110.0 | 19595 | 16335 |
3×240 | 10.5 | 103.5 | 13550 | 9140 | 112.5 | 17210 | 12800 | 115.2 | 22105 | 17820 |
3×300 | 10.5 | 108.7 | 15950 | 10290 | 117.7 | 19760 | 14100 | 120.8 | 25360 | 20280 |
3×400 | 10.5 | 115.5 | 19180 | 11830 | 125.1 | 23390 | 16080 | 127.8 | 31580 | 25050 |
Technical Data: Max. DC resistance & short circuit current of conductorNominal cross- sectional area of conductor (mm2) | 20ºC (Ω/KM) Max. DC resistance of conductor @ 20ºC | 90ºC (1) Max. Short circuit current of conductor (1s) @ 90ºC |
Copper conductor | Aluminum conductor | Copper conductor | Aluminum conductor |
25 | 0.727 | 1.20 | 3.58 | 2.36 |
35 | 0.524 | 0.868 | 5.01 | 3.31 |
50 | 0.387 | 0.641 | 7.15 | 4.72 |
70 | 0.268 | 0.443 | 10.02 | 6.61 |
95 | 0.193 | 0.320 | 13.59 | 8.98 |
120 | 0.153 | 0.253 | 17.17 | 11.34 |
150 | 0.124 | 0.206 | 21.46 | 14.317 |
185 | 0.0991 | 0.164 | 26.47 | 15.48 |
240 | 0.0754 | 0.125 | 34.6 | 22.68 |
300 | 0.0601 | 0.100 | 42.93 | 28.35 |
400 | 0.0470 | 0.0778 | 57.23 | 37.79 |
500 | 0.0366 | 0.0605 | 74.51 | 47.24 |
630 | 0.0283 | 0.0469 | 90.14 | 59.52 |
, Voltage test & Partial discharge testNo. | Test items | Rated voltage (KV) |
3.6/6 | 6/6 6/10 | 8.7/10 8.7/15 | 12/20 | 18/20 18/30 | 21/35 | 26/35 |
1 | (kv/5min) Power frequency AC voltage test | 12.5 | 21 | 30.5 | 42 | 63 | 73.5 | 91 |
2 | 4 AC voltage test for 4 hours (kV) | 14.4 | 24 | 35 | 48 | 72 | 84 | 104 |
3 | Impulse voltage test (kV) | 60 | 75 | 95 | 125 | 170 | 200 | 200 |
4 | 1.73U010PC Partial discharge at 1.73U0 voltage should not exceed 10 PC | Pass | Pass | Pass | Pass | Pass | Pass | Pass |
Current carrying capacity of CableConductor | Nominal cross- sectional area of conductor (mm2) | 3.6/6-12/20KV | 18/20-26/35KV |
In the air | Underground | In the air | Underground |
Single-core | 3-core | Single-core | 3-core | Single-core | 3-core | Single-core | 3-core | |
Copper conductor | 25 | 140 | 120 | 150 | 125 | - | - | - | - | |
35 | 170 | 140 | 180 | 155 | - | - | - | - | |
50 | 205 | 165 | 215 | 180 | 215 | 180 | 215 | 190 | |
70 | 260 | 210 | 265 | 220 | 270 | 220 | 265 | 230 | |
95 | 315 | 255 | 315 | 265 | 330 | 265 | 315 | 275 | |
120 | 360 | 290 | 360 | 300 | 380 | 305 | 360 | 315 | |
150 | 410 | 330 | 405 | 340 | 430 | 345 | 400 | 355 | |
185 | 470 | 375 | 455 | 380 | 490 | 390 | 455 | 400 | |
240 | 555 | 435 | 530 | 435 | 575 | 455 | 525 | 460 | |
300 | 640 | 495 | 595 | 485 | 660 | 525 | 595 | 520 | |
400 | 745 | 565 | 680 | 520 | 765 | 600 | 680 | 590 | |
500 | 855 | - | 765 | - | 875 | - | 775 | - | |
630 | 980 | - | 860 | - | 1010 | - | 875 | - | |
Aluminum conductor | 25 | 110 | 90 | 115 | 100 | - | - | - | - | |
35 | 135 | 110 | 135 | 120 | - | - | - | - | |
50 | 160 | 130 | 160 | 140 | 170 | 140 | 165 | 145 | |
70 | 200 | 165 | 200 | 170 | 210 | 170 | 200 | 180 | |
95 | 245 | 200 | 240 | 210 | 255 | 205 | 240 | 215 | |
120 | 280 | 225 | 270 | 235 | 295 | 235 | 270 | 246 | |
150 | 320 | 255 | 305 | 260 | 330 | 270 | 305 | 275 | |
185 | 365 | 295 | 345 | 300 | 380 | 305 | 345 | 310 | |
240 | 435 | 345 | 400 | 345 | 450 | 355 | 400 | 360 | |
300 | 500 | 390 | 455 | 390 | 515 | 410 | 455 | 410 | |
400 | 585 | 450 | 520 | 440 | 600 | 470 | 525 | 465 | |
500 | 680 | - | 595 | - | 695 | - | 600 | - | |
630 | 790 | - | 680 | - | 810 | - | 685 | - | |
Installation and operation condition of cable: Max. operating temperature of conductor:90ºCAmbient temperature in air:40ºCSoil temperature: 25ºCSoil thermal resitivity: 1.0ºCm/WLaying depth: 0.8mSingle-Circuit only,. Single-core cable is installed in parallel. Adjacent space is equivalent to the diameter of the cable. 0ºC.The ambient temperature under installation should not below 0ºC.Conversion factors of current rating for different ambient temperature :Air temperature | 20ºC | 25ºC | 30ºC | 35ºC | 40ºC | 45ºC | 50ºC |
Conversion factor | 1.18 | 1.14 | 1.10 | 1.05 | 1.00 | 0.95 | 0.89 |
Soil temperature | 15ºC | 20ºC | 25ºC | 30ºC | 35ºC | 40ºC | 45ºC |
Conversion factor | 1.07 | 1.04 | 1.00 | 0.96 | 0.92 | 0.87 | 0.83 |
Address:
Liangxu Town, Jiangyan Dist, Taizhou City, Jiangsu Province, China
Business Type:
Trading Company
Business Range:
Electrical & Electronics
Management System Certification:
ISO 9001, ISO 14001, OHSAS/ OHSMS 18001, ISO 10012
Company Introduction:
Founded in 1985
Our company is located in Taizhou, Jiangsu Province, and covering 180, 000. We own first-class production and testing facilities of 500 more sets, and our main products are power cables with voltage up to 35kV, pre-fabricated branch cables, new energy automotive cables, wind power cables, PV cables, nuclear power cables, aluminium alloy cables, fire-proof cables, submarine cables, computer cables, telecommunication cables, etc.
As a ′National New & High Technology Enterprise′, we are also honored as a ′heavy contract, keeping promises′ enterprise, ′Class AAA credit enterprise′, etc. And our products are awarded as ′National quality tracking and key protection products′. Besides, we can also design, develop and produce all kinds of products according to users′ requirements, and provide whole set of solution.
After accumulation and development of 30 more years, our company has built a completed marketing service network. Our products are widely applied to all kinds of engineering projects with good reputation, such as State Grid Corporation of China, new energy, rail traffic, railway, nuclear powder, chemical engineering, etc.
Sincerely look forward to cooperating with you, to create a bright future.